Outlet box · at the busway
Keep the receptacle at the overhead run and plug the equipment cord into the box.
All T225 outlet boxes →T225 · 225A TRACK BUSWAY SYSTEM
One phase conductor and neutral supply a single-phase, line-to-neutral load.
The standard T225 busway shown is a three-phase, four-wire system: L1, L2, L3 and neutral (N). Its grounded housing provides the separate equipment-grounding path.
The tap-off fitting connects the conductors needed for the unit’s circuit. The supply voltage and selected conductors determine the available voltage; the tap-off does not change voltage.
Fits T225 busway only. Match the unit’s ratings to your supply and load.
Keep the receptacle at the overhead run and plug the equipment cord into the box.
All T225 outlet boxes →Bring the receptacle closer to the equipment with a factory-configured cord drop.
All T225 drop cords →These tap-offs fit T225 busway. The system rating is up to 225A per phase, per feed; each tap-off has its own marked voltage, current and protection rating.
The factory-selected phase is L1–N, L2–N or L3–N. One phase selection applies to the entire tap-off, including all receptacles. Ground is separate from neutral.
For 120/240V or 415Y/240V projects, request a matching rated T225 assembly. Supply voltage alone does not establish product compatibility.
T225 tap-offs are factory wired and have no field-wiring terminals. Use the selected unit’s drawings and instructions for the actual connection.
The outlet-box guide covers its listed receptacle configurations. For a drop cord, use the technical documents for the selected drop-cord assembly.

The standard assembly carries three phases and neutral. The grounded housing provides the equipment-grounding path.
Model-based cutaway; supply routing is schematic. IG and 200% neutral configurations differ.
Explore T225 internal configurations →See the tap-off installed, unlocked, moved and secured again. This clip plays muted; use the controls to pause or enable sound.
Qualified personnel only. Keep the tap-off breaker OFF during installation, removal and relocation. Follow the T225 manual.
Watch the full T225 installation video →